Vacuum breakers sit at least 12 inches above the highest outlet. RPs stay above grade so they can drain. Every install leaves room for yearly testing.
- PriceFree quote
- TimeUsually 1 day
- TestIncluded
- FilingIncluded
What a good install looks like
- Vacuum breakers above the highest downstream outlet
- Clearance for testers and repairs
- Freeze and theft protection where needed
- RP assemblies above grade, never in a pit
Where an assembly should go
Where an assembly sits affects whether it can work and whether it passes inspection. RP assemblies must be installed above ground, with enough space under them for the relief valve to drain freely. Putting an RP in a pit or a box that floods is one of the most common mistakes we see.
Pressure vacuum breakers and spill-resistant vacuum breakers have to be higher than the highest sprinkler head or outlet they protect, usually by at least 12 inches. On hillside lots, that can mean placing the device near the top of the yard instead of by the meter.
Double checks have more flexibility and are sometimes placed in vaults, especially on fire lines, but they still need room to be tested and repaired.
Clearance and access
Every backflow assembly has to be tested every year, so it needs to be reachable. That means space around the test cocks for the gauge hoses, room to turn the shutoff valves and enough clearance to remove the check covers for repairs.
Devices wedged against walls, buried in shrubs or installed overhead in tight ceilings turn a 30-minute test into a two-hour job, or make repairs impossible without cutting pipe. We install with access in mind from the start.
We also think about who needs to reach it. A device behind a locked gate is fine for a home, but a commercial property might want it where a tester can get to it without an escort.
Protecting the device after it's in
Southern California doesn't freeze often, but it does happen in some inland and higher-elevation areas. A single cold night can crack a brass body or bonnet. Insulated covers or enclosures help where it's a risk.
Theft is a bigger concern in many neighborhoods. Brass backflow assemblies near streets and parking lots are targets for scrap thieves, and a stolen device leaves an open pipe and an urgent repair. Locking cages bolted to a concrete pad are the usual answer.
We'll recommend protection based on where the device is going. If you'd like a cage or cover, it can be added to the installation quote.
Startup test and the first report
After installation and flushing, we test the new assembly using the same procedure as the yearly test. It confirms the device is installed right and working.
We file that first passing report with your district. That puts the device on record and sets its first annual due date. A copy goes to you.
After that, it needs a test every year. Add due date management if you'd like us to track the date and schedule it for you.
Raising or relocating an existing assembly
Some assemblies were installed in the wrong spot years ago: an RP in a pit, a PVB below the sprinklers or a device boxed in where no one can test it. Moving it is often the right fix.
Relocation involves new piping and fittings, and the device is retested afterward. If the old device is in good shape, we can often reuse it, which keeps the cost down.
Installs on construction projects
On new construction and remodels, backflow installation is one piece of a bigger schedule. We work with general contractors, plumbers and landscape contractors to install the assembly when the site is ready and test it when water is available.
The startup test report is often needed for final inspection, so we make sure it's filed in time.
Choosing materials and fittings
What connects to the assembly matters as much as the assembly. We use potable-rated fittings sized to the device and add unions where they'll make later repairs simpler. Bigger assemblies get supports so the pipe isn't carrying the load.
Outdoors, we choose fittings that stand up to sun, soil and water. You won't see these choices on the report, but they decide whether the install lasts or starts leaking in a few years.
Once it's in
We test it right away and file the first report. After that, it needs an annual test.
Questions
Can an RP go underground?
No. The relief valve has to drain, so RPs go above ground.
Do you add a cage or cover?
If theft or freezing is a risk, we recommend one and include it in the quote.
Can a PVB go next to the meter?
Only if the meter is higher than every sprinkler it protects. On sloped yards it often needs to go uphill.
How long does installation take?
Most installs for 2-inch and smaller assemblies take a day.
Do you pour a pad for a cage?
Yes, when a cage is part of the job we include the pad it bolts to.
Can you move an existing assembly?
Yes. A moved assembly has to be retested afterward, and we include that.
Where we offer it
We provide backflow assembly installation in Westminster, Midway City, Stanton, Garden Grove, Fountain Valley and Cypress. Typical wait: under a week.
Why Westminster customers call us
Certified testers, calibrated gauges and district filing on every job. You get the price before any work and a copy of every report.
Testing is $105 per device under 4 inches and $175 for 4 inches and up. Other work is quoted free. Phones are answered 7 days a week, 6am to midnight, and emergency calls 24/7. Most visits are booked within the week.
A typical visit in Westminster: a confirmation call the day before, under an hour on site for the test, and the report filed the same day. When a test fails, the fix is usually a rebuild kit, done in one to two hours with the retest included. Bigger jobs like replacements and new installs get a free written quote first. Every report we file is also emailed to you, so your records stay complete.